Experiment and analysis on electromagnetic current transformer harmonic ratio error
DOI:
Author:
Affiliation:

1. College of Electrical Engineering and Automation, Fuzhou University, Fuzhou 350108, China; 2. Electric Power Research Institute, State Grid Fujian Electric Power Company, Fuzhou 350000, China

Clc Number:

TM452TH183.3

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    The harmonic transfer characteristics of electromagnetic current transformer is complex, and the transfer error varies and is hard to estimate. This article designs the experiment of hysteresis loop of ferromagnetic material, and analyzes the influence of the hysteresis loop shape on the transfer error of current transformer. Aiming at the difficulty of high accurate detection of harmonic error, a highprecision detection system of current transformer harmonic error was developed. With the experiment, the influence of frequency, load, fundamental current, harmonic phase and DC component on the harmonic transfer error of current transformer is analyzed.

    Reference
    Related
    Cited by
Get Citation
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:
  • Revised:
  • Adopted:
  • Online: July 19,2017
  • Published: