变压器铁芯搭接区磁热等效及温升影响研究*
DOI:
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

中图分类号TH81 文献标识码A国家标准学科分类代码: 4704017

基金项目:

*基金项目:基金项目国家自然科学基金(面上项目)(51477015)、重庆市教委高校创新团队项目(CXTDX201601019)资助


Research on magnetic heat equivalent and temperature rise of the lap area of transformer core
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    摘要:摘要针对变压器叠片铁芯接缝搭接区温升异常和损耗难以实测的问题,提出了搭接区等效损耗方法来实现对铁芯接缝处损耗突变的准确计算。首先建立铁芯接缝搭接区三维等效模型,通过梯度曲线确定搭接区等效范围,得出接缝区等效损耗(joint building factor, JBF)的计算公式,并研究了JBF的影响因素;然后建立考虑JBF的变压器整体温升模型,计算并分析开路试验下铁芯及结构件上的不同热点及特定曲线上的温升及影响因素;最后搭建了变压器铁芯温升试验平台实测接缝搭接区和夹件的热点温度,结果显示测量值和计算值的相对误差均小于250%,证明了计算方法的有效性。所提出的搭接区等效损耗计算方法为变压器铁芯损耗评估及工程设计提供了理论基础,对变压器安全运行和在线监测具有重要意义。

    Abstract:

    Abstract:There are abnormal temperature rise and difficult measurement of loss in the lap joint area of transformer laminated core joint. To solve these problems, this study proposes the joint building factor (JBF) method to obtain the accurate calculation ofloss mutation at the lap joint. Firstly, a threedimensional equivalent model of theoverlapped zoneof core joint isformulatedandtheequivalent rangeof theoverlapped zone isdeterminedbythegradient curve.Meanwhile,thecalculation formula of JBF is determinedandtheinfluencing factors of JBF are studied. Then, the whole temperature rise model of transformer considering JBF is established. The temperature rise and influence factors of different hot spots on iron core and structural parts under open circuit test are calculated and analyzed. Finally, the temperature rise test platform of transformer core is built to measure the temperature of joint lap area and hot spots of clamps. Experimental results show that the relative error between the measured value and the calculated value is less than 250%, which proves the effectiveness of the calculation method. Therefore, this method of equivalent loss in the lap area provides a theoretical basis for transformer core loss assessment and engineering design. It is of great significance for transformer safety operation and online monitoring.

    参考文献
    相似文献
    引证文献
引用本文

刘行谋,薛金鑫,杨永明,江帆,程鹏.变压器铁芯搭接区磁热等效及温升影响研究*[J].仪器仪表学报,2020,41(6):-196

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2022-03-01
  • 出版日期: